Fire Detection Specifications |
|
|
|
|
Range per channel |
2km |
4km |
8km |
10km |
Number of channels |
1/2/4 |
1/2/4 |
1/2/4 |
1/2/4 |
Data Acquisition |
|
|
|
|
Measuring time |
generally ~5 seconds for linear heat applications (EN54-22) |
|
|
|
Sampling Interval |
1m |
|
|
|
Temperature Resolution |
0.1°C@10s, 2km |
0.1°C@10s, 4km |
0.3°C@10s, 8km |
0.3°C@10s, 10km |
Temperature Accuracy |
±1°C |
|
|
|
Fiber Break Alarm |
Automatic detection, accuracy within < ±5m |
|
|
|
Optical |
|
|
|
|
Laser Wavelength |
1550 nm |
|
|
|
Optical Budget |
10 dB |
|
|
|
Connector Type |
E2000 |
|
|
|
Cable type |
Multi mode 62.5/125 |
|
|
|
Laser Safety Classification |
Class 1 |
|
|
|
Electrical and Hardware Interfaces |
|
|
|
|
Supply Voltage |
24VDC |
|
|
|
Power Consumption |
85W (max) |
|
|
|
Relays |
Yes - 48 NO/NC relays |
|
|
|
Modbus |
MODBUS TCP / MODBUS RTU |
|
|
|
Serial |
1x RS-485 - 1x RS-232 |
|
|
|
USB |
1x USB |
|
|
|
Other |
7.0-inch touch screen, 1024*600-pixel |
|
|
|
Internal Storage |
> 500,000 measurements @10km |
|
|
|
|
|
|
|
|
Physical Properties |
|
|
|
|
Rack Height |
3U |
|
|
|
Dimensions (W * H * D) |
485 x 133 x 509 mm |
|
|
|
Net Weight |
10 kg |
|
|
|
IP Rating |
IP40 |
|
|
|
Material |
Painted Galvanized Steel |
|
|
|
Colour/Finish |
Matt Black |
|
|
|
Shipping Dimensions |
12 kg |
|
|
|
Shipping Weight |
|
|
|
|
Environmental Properties |
|
|
|
|
Operating Temperature |
-10°C to +55°C |
|
|
|
Operating Humidity |
0 to 95%RH |
|
|
|
Storage Temperature |
-10°C to +85°C |
|
|
|
Storage Humidity |
0 to 95% Relative Humidity, Non-condensing |
|
|
|
Software |
|
|
|
|
Software Name |
FOTAS Web |
|
|
|
Alarm Types |
Max & Min, Rate of Rise and Deviation |
|
|
|
Max. Zones |
1000 |
|
|
|