DTS-L Single Channel Linear Heat Detection System

DTS-L is a fiber optic temperature sensing system designed for efficient leak detection and fire monitoring. It ensures safety by providing early warnings of leaks and detecting a wide range of substances, such as gases or liquids, along extended distances spanning several kilometers.

S-10 Technical Details

Fiber Optic Cable Single-mode fiber optic cable
Detection Channels Single fiber channel of real time independent intrusion detection
Detection Distance 10 km
Sensing Technology Coherent Optical Time Domain Reflectometer (COTDR)
Maximum Fiber Loss 10dB (typical max distance ~ 10km /ch)
Operating Life > 10 years (dependent on operating environment and regular maintenance)
Artificial Intelligence Deep-learning-based intrusion detection algorithms optimize sensitivity and probability of detection. Locations can be changed with parameters to avoid nuisance alarms. Different algorithms exist for buried and fence applications. The system is hybrid since both are applicable.
Detection Resolution 10 m (32.8 ft) between detection points along sensing fiber (100 measurements per km of sensing fiber) 100 m (328 ft) minimum cable separation between individually reported disturbances (simultaneous)
System Interface Web 2.0
Sensor Sections Software configurable, independent sensor sections (detection zones).
Temperature Range Sensing Cable: -40~70 °C / S-10 Device: 0~40 °C (AC environment)
Connection Ports TCP/IP (Ethernet)
Inputs and Outputs FC/APC single mode optical connector (back, for sensing cable) 1 x USB2 ports (on back) 1 x Ethernet ports (10/100/1000 Mbps, on back)
Power Supply 110 to 240 Vac, 47 to 63 Hz, auto ranging.
Power Consumption 85 W typical, 125 W max
Dimensions / Rack -Clearance / Weight 49 cm (19”) x 50 cm x 8.9 cm(2U), 8 kg
Laser Safety Class Class 1 (IEC 60825-1, 21CFR1040.10), shutoff: key switch on front panel.
MTBF > 80,000 hours
Warranty 2 years, with optional per year warranty extension available.
Regulatory Certification ISO9001 accredited design and manufacturing is CE certified (Electromagnetic compatibility Directive (EMC) 2014/30/EU (EN 55032:2015 Class A, EN IEC 61000-3-2:2019+A1:2019, EN 61000-3-3:2013+A1:2019, EN 55035:2017+A1:2020, EN 61000-4-2:2009, EN 61000-4-3:2020, EN 61000-4-4:2012, EN 61000-4-5:2014+A1:2017, EN 61000-4-6:2014, EN 61000-4-8:2010, EN 61000-4-11:2020) The low voltage directive (LVD) (2014/35/EU) (IEC 62368-1:2018, EN IEC 62368-1:2020 + A11:2020)